Winding movement in power transformers: a comparison of FRA measurement connection methods

Деформации обмоток в силовых трансформаторах: сравнение методов подключения при измерениях FRA
J.A.S.B. Jayasinghe, Zhongdong Wang, Paul Jarman, A. Darwin
2006-12-01

132/11 kV 30 MVA transformerHV neutral groundedaxial bendingaxial displacementend-to-end voltage ratioforced bucklingfrequency response analysisinput admittancetransfer voltage ratiowinding movement sensitivity
Frequency response analysis (FRA) is an effective diagnostic tool for detecting transformer winding movements. Various FRA traces can be measured from a set of transformer winding terminals each of which relate to a different test connection scheme. Practical considerations of test and analysis time dictate that only some of the connections are used, and currently there is no standard test connection. This paper presents a comparison of three FRA measurement connections widely employed in the industry today, namely: end-to-end voltage ratio, input admittance and transfer voltage ratio measurements. Using a simulation model of a 132/11 kV, 30 MVA transformer, FRA traces were generated under these connection schemes and their sensitivity towards three types of winding movement, namely: axial displacement, forced buckling and axial bending was studied. A correlation exists between the FRA measurement results of end-to-end voltage ratio, input admittance and transfer voltage ratio connection methods, provided that the HV neutral is grounded. Among the three connection methods assessed, the transfer voltage ratio connection method has the best sensitivity to axial displacement and forced buckling, whereas the end-to-end voltage ratio method has the best sensitivity towards axial bending
1
A correlation exists between results of the three connection methods when the HV neutral is grounded.
2
End-to-end voltage ratio shows the best sensitivity to axial bending.
3
FRA traces were generated from a simulation model of a 132/11 kV, 30 MVA transformer to compare three measurement connections.
4
Three FRA connection methods compared: end-to-end voltage ratio, input admittance, and transfer voltage ratio.
5
Transfer voltage ratio shows the best sensitivity to axial displacement and forced buckling.

Power transformer windings (of a 132/11 kV, 30 MVA transformer) as measured by different FRA connection schemes

Sensitivity and correlation of three FRA measurement connection methods (end-to-end voltage ratio, input admittance, transfer voltage ratio) for detecting winding movements (axial displacement, forced buckling, axial bending) under grounded HV neutral conditions

Publication Details
Publication Date
2006-12-01
Journal
Publisher
ISSN
Access Type
Author Information
Authors
J.A.S.B. Jayasinghe
Zhongdong Wang
Paul Jarman
A. Darwin
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat
Make a presentation
100%