A Novel Scalar PWM Method to Reduce Leakage Current in Three-Phase Two-Level Transformerless Grid-Connected VSIs

Новый скалярный метод ШИМ для уменьшения тока утечки в трехфазных двухуровневых трансформаторнобезопасных VSИ, подключенных к сети
Houjun Tang, Junzhong Xu, Jingwen Han, Yong Wang, Salman Habib
2019-06-07

dc-link current harmonicleakage current reductionscalar PWMtransformerless three-phase two-level grid-connected voltage source inverterszero-sequence voltage generation
The advancement in modulation strategies brings emergent solutions to suppress the leakage current in three-phase two-level transformerless grid-connected voltage source inverters (VSIs). However, most of the techniques are analyzed based on reduced common-mode voltage pulsewidth modulation (PWM) in motor drivers but fail to satisfy the specific requirement of grid-connected applications, such as wider power factor operation and lesser current distortion. To overcome such substantial drawbacks, this paper proposes a novel scalar PWM method for transformerless grid-connected VSIs. First, presented through a generalized scalar approach with unified zero-sequence voltage generation, the method is simple to implement and favored in practice. Besides, systematic and comprehensive mathematical analysis is illustrated to exhibit the validity of implemented method in reducing leakage current and shows its advantages over whole power factor range in terms of dc-link current harmonic, output current quality, and switching losses. Finally, simulations and experimental results are carried out to verify the effectiveness and superiority of the proposed method.
1
A novel scalar PWM method is proposed specifically for three-phase two-level transformerless grid-connected VSIs to reduce leakage current.
2
Mathematical analysis shows the method reduces leakage current and outperforms reduced common-mode PWM techniques across the whole power factor range.
3
Simulations and experimental results verify the effectiveness and superiority of the proposed scalar PWM method.
4
The method uses a generalized scalar approach with unified zero-sequence voltage generation, making it simple to implement in practice.
5
The proposed method improves dc-link current harmonic, output current quality, and switching losses compared to existing approaches.

Three-phase two-level transformerless grid-connected voltage source inverter (VSI) system

Effectiveness of a novel scalar PWM method with unified zero-sequence voltage generation to reduce leakage current and improve dc-link current harmonics, output current quality, and switching losses across the whole power-factor range in grid-connected VSIs

Publication Details
Publication Date
2019-06-07
Journal
Publisher
ISSN
Access Type
Author Information
Authors
Houjun Tang
Junzhong Xu
Jingwen Han
Yong Wang
Salman Habib
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat
Make a presentation
100%