Behaviour of refrigerant mixtures with gas/liquid injection

Samuel M. Sami, Shawn Aucoin
2003-01-01

SCID:  54.1/zgf59vxa
In this paper, the impact of gas/liquid injection on the behaviour of new alternative refrigerant mixtures such as; R-410A, R-507, R-407C, and R-404A are discussed, analysed and presented. The test results were obtained using an air–source heat pump set up with enhanced surface tubing heat exchanger under various gas/liquid injection ratios. Performance tests were conducted according to the ARI/ASHRAE Standards. The performance data demonstrated that as gas/liquid injection increases compressor head pressure and discharge temperature decrease and this has a positive effect in protecting the compressor. The effect of gas/liquid injection on mixture behaviour varies from mixture to another depending upon the mixture composition. Furthermore, hot gas injection appears to have a significant and positive influence on the COP. The performance of refrigerants R-407C and R-404A has been enhanced with 5% gas injection and mix of gas and liquid 5% injection, respectively. The data presented in these figures also show that other hot gas injection ratios and gas/liquid mix degrade the heat exchanger performance. Copyright © 2003 John Wiley & Sons, Ltd.
Publication Details
Publication Date
2003-01-01
Journal
Publisher
ISSN
Access Type
Author Information
Authors
Samuel M. Sami
Shawn Aucoin
Explore More Research
Use the citation graph to discover related papers and expand your research horizons.
Click any node to explore
Download PDF
100%