Risk Assessment of Toxic Gas Dispersion from Electric Vehicle Fires in Underground Apartment Parking Garages Using Numerical Analysis

Оценка риска распространения токсичных газов при пожарах электромобилей на подземных парковках многоквартирных домов с использованием численного анализа
J.S. Jang, Joonho Jeon, Chang Bo Oh
2025-02-25

Fire Dynamics Simulator (FDS)electric vehicle fireshydrogen fluoride (HF)toxic gas dispersionunderground parking garages
With the rising adoption of electric vehicles (EVs), fire-related issues have garnered significant attention, prompting extensive research efforts. This study investigates the dispersion of toxic gases generated during EV fires in confined spaces, such as underground parking garages, to enhance fire safety protocols. Using the fire dynamics simulator (FDS), simulations were conducted for 24 kWh, 53 kWh, and 99.8 kWh battery scenarios to assess the impact of increasing battery capacities on toxic gas emissions. The results indicate that hydrogen fluoride (HF) concentrations in poorly ventilated areas peaked at 488.2 ppm, significantly exceeding the Acute Exposure Guideline Level (AEGL-2) threshold of 12 ppm. The exposure time exceeding AEGL-2 (30 min) was recorded as 53 min and 49 s for the 99.8 kWh scenario, highlighting a substantial risk to occupants and emergency responders. Additionally, the fractional effective dose (FED) for asphyxiant gases and the fractional effective concentration (FEC) for irritant gases were analyzed, revealing that larger battery capacities and proximity to the fire source reduced tenability time by up to 47% compared to smaller batteries. These findings provide critical insights into fire safety measures, emphasizing the necessity of early fire detection systems, enhanced ventilation strategies, and battery-specific fire suppression technologies in confined environments.
1
FDS simulations assessed toxic-gas dispersion from 24 kWh, 53 kWh, and 99.8 kWh EV battery fires in underground parking garages.
2
For the 99.8 kWh scenario, HF exposure above AEGL-2 lasted 53 minutes 49 seconds, posing substantial risks to occupants and responders.
3
Larger battery capacities and closer proximity to the fire reduced tenability time by up to 47%, based on FED and FEC analyses.
4
Poorly ventilated areas reached peak hydrogen fluoride concentrations of 488.2 ppm, far exceeding the AEGL-2 threshold of 12 ppm.
5
The results support early fire detection, improved ventilation, and battery-specific suppression technologies for confined parking environments.

Toxic gas dispersion from electric vehicle fires in underground apartment parking garages

The effects of EV battery capacity, ventilation conditions, and proximity to the fire source on toxic-gas concentrations, exposure duration, and occupant tenability

Publication Details
Publication Date
2025-02-25
Journal
Publisher
ISSN
Cited by
8
Access Type
Author Information
Authors
J.S. Jang
Joonho Jeon
Chang Bo Oh
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%