Saturation of Current Transformers and its Impact on Digital Overcurrent Relays
Насыщение трансформаторов тока и его влияние на цифровые реле максимального тока
2006-01-01
SCID: 54.1/kr2uqewy
Discuss with AI
current transformer saturationdigital overcurrent relaysinstantaneous overcurrent protectionprotection coordinationtime-delayed overcurrent relays
Figures from the paper
Abstract (AI)
Improper selections of current transformers will result in CT's saturation during fault conditions which can affect protection relays operations. With the absence of clear and practical guidelines for CT's selections, designers are facing great difficulties to ensure proper operations of digital relays. The impact of CT saturation is different for different protection devices and schemes. This paper investigates the influence of CT saturation on over-current digital relays, in distribution systems where loads are relatively small and connected to switch-gears with high short circuit levels. A research was performed to verify the operations of instantaneous and time-delayed over-current digital relays to ensure coordination with other devices and safe isolations of faults. It is shown that instantaneous digital relays will perform properly with a relatively small CT's. A criterion for selecting CT's for instantaneous digital over-current relays operations is presented. However, time-delayed over-current relays will be significantly impacted by CT's saturation and special care shall be taken to achieve coordination with other devices
Key Findings
1
Improper current-transformer selection can cause saturation during faults, altering digital overcurrent relay operation and complicating protection coordination.
2
Instantaneous digital overcurrent relays can operate properly with relatively small current transformers under the investigated conditions.
3
The paper presents a CT-selection criterion specifically intended to support proper operation of instantaneous digital overcurrent relays.
4
The study evaluates CT saturation effects on instantaneous and time-delayed digital overcurrent relays in distribution systems with low loads and high short-circuit levels.
5
Time-delayed overcurrent relays are significantly affected by CT saturation, requiring special attention to maintain coordination and safe fault isolation.
Research Object
digital overcurrent relays in distribution systems with current transformers under fault conditions
Research Subject
the influence of current-transformer saturation on instantaneous and time-delayed relay operation, fault isolation, and coordination with other protection devices
Publication Details
Publication Date
2006-01-01
Journal
Publisher
ISSN
Open access PDF
Access Type
Author Information
Download PDF
Subscribe to digest