Impact of current transformer saturation on overcurrent protection operation

Влияние насыщения трансформаторов тока на работу максимальной токовой защиты
Lj. A. Kojovic
2003-06-25

CT burdencurrent transformer saturationfault conditionsovercurrent protectionprotection device coordination
If current transformer (CT) characteristics are not properly selected for fault conditions, saturation will occur which can affect protection device operation. In some applications even if CTs are properly sized, it is necessary to locate protection devices far from the CTs. In these cases, the wire resistance, which adds to the CT burden, causes CT saturation at smaller currents than when located close to the protection devices. The impact of CT saturation on protection device operation is different for different protection device types and protection schemes. This paper investigates the influence of CT saturation on overcurrent protection when protection devices are located far from the CTs, causing their saturation during faults. A study was performed to verify that delayed overcurrent protection response will not cause mis-coordination with other protection devices. It is shown that CT saturation will not significantly delay overcurrent protection operation for most common settings.
1
A study found that delayed overcurrent protection response from CT saturation generally does not cause mis-coordination with other protection devices.
2
For most common settings, CT saturation does not significantly delay overcurrent protection operation.
3
Inadequately selected CT characteristics can cause saturation during faults and affect overcurrent protection operation.
4
Long distances between current transformers and protection devices increase wire resistance and CT burden, causing saturation at lower fault currents.
5
The impact of CT saturation depends on the protection-device type and protection scheme.

Overcurrent protection systems with current transformers located far from protection devices during faults

The influence of current-transformer saturation, caused by CT burden and remote wiring resistance, on overcurrent protection response delay and coordination

Publication Details
Publication Date
2003-06-25
Journal
Publisher
ISSN
Cited by
32
Access Type
Author Information
Authors
Lj. A. Kojovic
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%