LITHIUM-ION BATTERY FIRE SUPPRESSION USING WATER MIST SYSTEMS

Тушение пожаров литий-ионных аккумуляторов с использованием систем водяного тумана
Matt Ghiji, Ian Burch, Grant Gamble, Vasily B. Novozhilov, Paul F. Joseph, Khalid Moinuddin
2021-10-14

18650 cellscone calorimeterelectrolyte thermal behaviorlithium-ion battery fireswater mist fire suppression
Lithium-ion batteries (LiBs) have superior energy density and lifetime compared to battery technologies such as lead acid.Despite the widespread application of LiBs in energy storage systems, electronic devices, aerospace and the automotive industry, they present a fire risk.In this study, experiments were conducted to characterize the thermal behavior of the electrolyte (as the main contributor to LiB fires) using a cone calorimeter; investigate the interactions of water mist and a Bunsen burner, as a precursor to examining the effectiveness of a water mist suppression system in extinguishing a LiB fire.In the present work, we have endeavored to systematically study the fire suppression efficacy of water mist by adopting to some novel approaches.This involved carefully planned laboratory scale explorations that involved a propane gas fueled flame, and subsequently by using bespoke set up that mimicked fire owing to fuel surge from typical Li-ion cell (18650 cells).In the latter set of fire suppression tests, water droplets were produced by a fan nozzle and sprayed horizontally toward the jet flame of replica 18560 battery containing only the electrolyte.The results showed that both fire types (Bunsen burner and LiB) are suppressed rapidly on activation of the water mist fire suppression system for geometries that enable the water mist direct access to the lift-off zone, between the gas source and base of the flame.
1
A bespoke electrolyte-only replica-cell setup was used to evaluate horizontal fan-nozzle water-mist application against lithium-ion battery fire behavior.
2
Experiments examined water-mist interactions with both propane Bunsen flames and electrolyte-fueled flame surges simulating 18650 lithium-ion cells.
3
Suppression effectiveness depended strongly on system geometry, specifically enabling droplets to reach the region between the fuel source and flame base.
4
The study characterized lithium-ion battery electrolyte thermal behavior using cone-calorimeter experiments, identifying it as a major contributor to battery fires.
5
Water mist rapidly suppressed both Bunsen-burner and simulated lithium-ion battery fires when the spray directly accessed the flame lift-off zone.

Lithium-ion battery electrolyte jet flames and their suppression by a water mist system

Thermal behavior of the electrolyte and the effectiveness of water mist in rapidly suppressing the flames, including the influence of direct access to the flame lift-off zone

Publication Details
Publication Date
2021-10-14
Journal
Frontiers in Heat and Mass Transfer
Publisher
Global Digital Central
ISSN
2151-8629
Cited by
9
Access Type
Author Information
Authors
Matt Ghiji
Ian Burch
Grant Gamble
Vasily B. Novozhilov
Paul F. Joseph
Khalid Moinuddin
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%