Avoid Current Transformer Saturation Using Adjustable Switched Resistor Demagnetization Method
Предотвращение насыщения трансформатора тока с использованием метода размагничивания с регулируемым переключаемым резистором
2020-04-01
SCID: 54.1/p3zcvkuq
Discuss with AI
CT secondary current derivativeadjustable resistorcurrent transformer saturationshort-circuit faultsswitched resistor demagnetization
Figures from the paper
Abstract (AI)
In some conditions, the flux in the core of current transformers (CT) increases. If this increase in flux leads to saturation of the protective core, it can create a lot of problems in power system protection. One of the hardware solutions to prevent the occurrence of core saturation in CT is the fixed switched resistor demagnetization method. Due to disadvantages such as dependence on CT parameters and inefficiencies in severe core saturation, the use of this method has not been expanded. This paper proposes a new method to improve the fixed switched resistor demagnetization method. In the proposed method, instead of using a fixed resistor in the circuit topology, an adjustable resistor with an auxiliary transformer is used. In the previous method, the control process is based on flux estimation from the secondary terminal voltage. The control process in the proposed method is based on the second derivative of CT secondary current. To verify the effectiveness of the suggested method, first simulation is done using COMSOL and MATLAB softwares and then all necessary electronic and control circuitry are designed and built. Experimental test is carried out on a 20 kV- 500/5 A CT. The simulation and experimental results show that this method prevents the CT from saturation in case of short circuit faults. The main advantages of this method are independent to CT parameters and efficient in severe core saturation.
Key Findings
1
An adjustable switched-resistor demagnetization method with an auxiliary transformer is proposed to improve fixed-resistor CT saturation prevention.
2
COMSOL and MATLAB simulations, followed by hardware implementation and testing on a 20 kV, 500/5 A CT, validate the method.
3
Simulation and experimental results show that the method prevents CT saturation during short-circuit faults.
4
The method is reported to be independent of CT parameters and effective under severe core saturation, addressing key limitations of fixed-resistor demagnetization.
5
The proposed control strategy uses the second derivative of CT secondary current instead of estimating flux from secondary terminal voltage.
Research Object
protective-core current transformers (CTs) under short-circuit fault conditions
Research Subject
prevention of core saturation using adjustable switched-resistor demagnetization controlled by the second derivative of secondary current