Compensation of the Current-Transformer Saturation Effects for Digital Relays
Компенсация эффектов насыщения трансформатора тока для цифровых реле
2011-08-25
SCID: 54.1/yd84d585
Discuss with AI
current transformer saturationdigital protective relaysleast error squares filterphasor estimationsaturation compensation
Figures from the paper
Abstract (AI)
A current transformer (CT) is accurately modeled for representation of the CT saturation effects on digital protective relays. Simulation studies performed in the PSCAD/EMTDC platform are used to investigate the impacts of CT saturation on the current phasor estimation. A new algorithm is also proposed for detection and compensation of CT saturation effects, based on: a least error squares (LES) filter which estimates the phasor parameters of the CT secondary current; a novel saturation detection method which uses the output of the LES filter for saturation detection; and a new minimum estimation error tracking approach which enhances the precision of the phasor estimation. The proposed saturation detection/compensation algorithm is independent of the parameters of the CT, the burden, and the power system. The study results show that the proposed algorithm: 1) reconstructs the distorted current waveform, under dc and ac saturation conditions, with the required precision and speed and 2) performs satisfactorily under inductive burden and under deep and slight saturation conditions.
Key Findings
1
A new compensation algorithm combines a least error squares filter, output-based saturation detection, and minimum estimation-error tracking.
2
PSCAD/EMTDC simulations demonstrate that CT saturation distorts current phasor estimation under investigated operating conditions.
3
The algorithm is independent of CT parameters, burden characteristics, and power-system parameters.
4
The method reconstructs distorted current waveforms accurately and quickly under DC and AC saturation, including deep, slight, and inductive-burden conditions.
5
The study develops an accurate current-transformer model to represent CT saturation effects on digital protective relay current-phasor estimation.
Research Object
current-transformer saturation effects on digital protective relays and current phasor estimation
Research Subject
distortion of secondary-current waveforms and resulting phasor-estimation errors, including their detection and compensation under DC and AC saturation conditions
Publication Details
Publication Date
2011-08-25
Journal
Publisher
ISSN
Cited by
80
Access Type
Author Information
Download PDF
Subscribe to digest
References available in scid.ai1
Cited by5
Current-Transformer Saturation Compensation for Transformer Differential Relays2015
Prevention of the current transformer saturation by using negative resistance2020
Avoid Current Transformer Saturation Using Adjustable Switched Resistor Demagnetization Method2020
Current Transformer Saturation Compensator by Using Negative Voltage Feedback2019
Fast Detection and Compensation of Current Transformer Saturation Using Extended Kalman Filter2019