Full-Scale Fire Suppression Experiment of a Water-Based Extinguishing System for Electric Vehicle Fire Response

Полномасштабное испытание системы пожаротушения на водной основе для тушения пожаров электромобилей
Byeong-Cheol Kim, Byung-Yong Ko, Kuk-il Han, Jae-Woo Chung
2024-12-31

battery cell typeelectric vehicle firesthermal runawayundercarriage sprinkling systemwater-based extinguishing system
The distribution of electric vehicles (EVs) in South Korea continues to expand owing to government policies aimed at reducing greenhouse-gas emissions and fostering future industries. As of July 2024, 621,000 EVs were registered, with 1.32 fire incidents reported per 10,000 vehicles in 2023. A two-stage experiment was conducted to verify the fire suppression and control performance of the sprinkler and undercarriage sprinkling systems, which are the basic fire safety facilities for responding to EV fires. The experiment also targeted EVs with different battery types and included a lower two-line sprinkling system, which was not used in previous experiments. In the first stage, a domestic EV equipped with pouch-type batteries was tested using the upper sprinkler and lower two-line sprinkling system. In the second stage, a foreign EV equipped with cylindrical batteries was tested using the upper sprinkler and lower one-line sprinkling system. The results showed that in the first and second stages, the battery loss rates were approximately 30%, and 100%, respectively. Although various experimental conditions affected the thermal runaway duration, loss rate, and fire spread to adjacent vehicles, cooling the battery pack using both the upper and lower water-based extinguishing systems delayed thermal runaway and effectively prevented the spread of fire. Notably, the lower sprinkling system showed differences in thermal runaway duration and fire-suppression performance depending on the battery cell type.
1
A two-stage full-scale experiment evaluated upper sprinklers and undercarriage sprinkling systems for suppressing and controlling electric-vehicle fires.
2
Battery loss rates were approximately 30% for the pouch-battery EV and 100% for the cylindrical-battery EV under the respective test conditions.
3
Cooling the battery pack with both upper and lower water-based systems delayed thermal runaway and effectively prevented fire spread to adjacent vehicles.
4
The experiments covered domestic EVs with pouch-type batteries and foreign EVs with cylindrical batteries, including a previously untested lower two-line sprinkling configuration.
5
The lower sprinkling system’s thermal-runaway duration and fire-suppression performance varied according to battery cell type.

Electric vehicles with pouch-type or cylindrical battery packs subjected to full-scale fire experiments

Fire suppression and control performance of combined upper sprinkler and undercarriage water-based sprinkling systems, including effects on thermal runaway, battery loss, and fire spread

Publication Details
Publication Date
2024-12-31
Journal
Publisher
ISSN
Cited by
2
Access Type
Author Information
Authors
Byeong-Cheol Kim
Byung-Yong Ko
Kuk-il Han
Jae-Woo Chung
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%