Full-Scale Fire Extinguishing Experiments to Analyze the Adaptability of Firefighting Facilities for Electric Vehicle Fires in Underground Parking Lots

Полномасштабные эксперименты по тушению пожаров для анализа адаптивности противопожарных систем к пожарам электромобилей на подземных парковках
Byung-Yong Ko, Sun-Hwa Yoo, Dae-Hyun Choi, Kukil Han
2024-04-30

electric vehicle firesfire extinguishing experimentspre-action sprinkler systemthermal runawayunderground parking lots
Recently, the number of electric vehicles (EVs) has rapidly increased owing to an increase in international environmental problems and domestic eco-friendly policies. With the increase in the number of EVs, the number of EV fires is also increasing. However, full-scale experiments for fire risk analysis or verification studies on the adaptability of present firefighting facilities are lacking , except for EV fire suppression experiments. In this study, to analyze the adaptability of firefighting facilities to EV fires in underground parking lots, fire extinguishing experiments on EV fires were conducted by considering the conditions of firefighting facilities applied to existing buildings. The first experiment simulated a current underground parking sprinkler system (pre-action system). In the second experiment, a lower sprinkler system was added to the upper sprinkler system. Experiment #1 confirmed that preventing the spread of thermal runaway in EV battery packs was difficult but blocking fire spread to adjacent vehicles was possible. Experiment #2 confirmed that thermal runaway occurred in approximately 50% of EV battery packs. These experiments concluded that fire spread to adjacent vehicles could be blocked by the spray from the upper sprinkler system.
1
Adding a lower sprinkler system resulted in thermal runaway in approximately 50% of EV battery packs.
2
Despite battery-pack thermal runaway, sprinkler discharge prevented fire spread to adjacent vehicles.
3
Full-scale experiments evaluated whether existing underground-parking firefighting facilities can manage electric vehicle fires.
4
Overall, the upper sprinkler system was sufficient to block fire spread from burning EVs to neighboring vehicles.
5
The current pre-action sprinkler system could not prevent thermal-runaway propagation within EV battery packs.

Electric vehicle fires in underground parking lots under existing-building firefighting facility configurations

Adaptability of upper and lower sprinkler systems for suppressing thermal runaway and preventing fire spread to adjacent vehicles

Publication Details
Publication Date
2024-04-30
Journal
Fire science and engineering
Publisher
ISSN
1738-7167
Cited by
7
Access Type
Author Information
Authors
Byung-Yong Ko
Sun-Hwa Yoo
Dae-Hyun Choi
Kukil Han
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%