Numerical Evaluation of Local Smoke and Thermal Responses to Prescribed Smoke Extraction and Matched Water-Spray Arrangements in an Underground Parking Garage
Численная оценка локальных дымовых и тепловых откликов на заданные режимы дымоудаления и согласованные схемы водяного распыления в подземном гараже
2026-08-14
SCID: 54.1/xmr7zfef
Discuss with AI
EV firesFire Dynamics Simulator (FDS)smoke extractionunderground parking garageswater-spray arrangements
Figures from the paper
Abstract (AI)
Electric vehicle (EV) fires can rapidly affect smoke and thermal conditions in underground parking garages. In this study, fifteen PyroSim/FDS cases were screened, but quantitative analysis was restricted to four prescribed-extraction cases and one baseline-matched two-device spray pair. The 0.30 m production mesh was selected using characteristic-fire-diameter, geometric-resolution, and computational-cost criteria. A matched 0.20/0.30/0.50 m check yielded non-monotonic fixed-point responses; mesh independence was not established. Extraction cases were compared using 270–300 s means and the first downward crossing of a 10 m visibility reference. At the same nominal outflow of 10 m3/s, two 5 m/s surfaces produced lower M1 gas temperature and CO and higher visibility than one 10 m/s surface. Relocating the second spray device beneath the vehicle reduced the τ = 120–150 s mean M4 underside-region gas temperature from 776.5 to 103.4 °C, while M1 visibility remained about 0.22 m. Because the model lacks a physical make-up-air path and corresponding experiments were not reproduced, these findings are limited to local prescribed-boundary comparisons. Relevant experiments support the represented mechanisms but the results do not validate the absolute point values. The simulations do not demonstrate battery extinguishment, maintained tenability, or code compliance.
Key Findings
1
A 0.30 m production mesh was selected using fire-diameter, geometric-resolution, and computational-cost criteria, but mesh independence was not established.
2
At equal nominal extraction flow of 10 m3/s, two 5 m/s extraction surfaces produced lower M1 gas temperature and CO and higher visibility than one 10 m/s surface.
3
Relocating the second spray device beneath the vehicle reduced the τ = 120–150 s mean M4 underside-region gas temperature from 776.5 to 103.4 °C, while M1 visibility remained approximately 0.22 m.
4
The results do not demonstrate battery extinguishment, maintained tenability, code compliance, or validation of absolute point values.
5
The simulations represent local prescribed-boundary comparisons because they lack a physical make-up-air path and do not reproduce corresponding experiments.
Research Object
Smoke extraction and water-spray arrangements in an underground parking garage during electric-vehicle fire scenarios
Research Subject
Local smoke and thermal responses, including gas temperature, CO concentration, and visibility, to prescribed extraction and matched spray-device placement
Publication Details
Publication Date
2026-08-14
Journal
Fire
Publisher
Multidisciplinary Digital Publishing Institute
ISSN
2571-6255
Cited by
0
Open access PDF
Access Type
Author Information
Download PDF
Subscribe to digest
References available in scid.ai3
Full-scale fire testing of battery electric vehicles2022
Full-Scale Fire Testing to Assess the Risk of Battery Electric Vehicle Fires in Underground Car Parks2025
Full-Scale Fire Extinguishing Experiments to Analyze the Adaptability of Firefighting Facilities for Electric Vehicle Fires in Underground Parking Lots2024