Prevention of the current transformer saturation by using negative resistance

Предотвращение насыщения трансформатора тока с использованием отрицательного сопротивления
Saeed Sanati, Yousef Alinejad‐Beromi
2020-11-20

current transformer saturationhigh-order harmonicsnegative resistanceprotection relayssecondary-side voltage compensation
Abstract In the power grid, various conditions may occur that saturate the core of a current transformer. Saturation of the protection core of the current transformers can cause a malfunction in the protection relays. To prevent malfunction of the protection relays caused by the current transformer saturation, software and hardware methods can be used. In the software method changes in the protection relay algorithm are used. In the hardware method special devices are used. A new hardware method is presented here, which uses compensation to prevent the occurrence of current transformer saturation. In the proposed method, compensation is done by controlling an applied voltage to the current transformer secondary terminals using negative resistance. The proposed method, despite its simplicity and cost‐effectiveness, has good performance in preventing saturation in various conditions. The high reliability in terms of the risk of secondary open circuit and its application in various saturation conditions, even in the case of severe saturation are the main advantages of the proposed method. Also, the proposed method does not produce distortion in the transformation of high‐order harmonics by the current transformer. To verify the effectiveness of the proposed method, prototype design and construction have been performed. The simulation and experimental results of laboratory tests have been presented and analysed.
1
A new hardware method prevents current-transformer core saturation by controlling the secondary-terminal voltage through negative-resistance compensation.
2
Prototype construction, simulations, and laboratory experiments were used to verify the method’s effectiveness.
3
The approach remains applicable during severe saturation and offers high reliability regarding the risk of a secondary open circuit.
4
The method is described as simple and cost-effective while maintaining good saturation-prevention performance under various operating conditions.
5
The proposed compensation does not distort the current transformer’s transformation of high-order harmonics.

protection-core current transformers in power-grid conditions

prevention of current-transformer core saturation and the resulting protection-relay malfunction using negative-resistance voltage compensation, including performance, reliability, and harmonic-transformation fidelity

Publication Details
Publication Date
2020-11-20
Journal
Publisher
ISSN
Access Type
Author Information
Authors
Saeed Sanati
Yousef Alinejad‐Beromi
Explore further
Open the scid.ai AI chat with a ready-made request: it will find papers on a similar topic and help build a literature review.
Find similar papers in the chat →
Make a presentation
100%