Current-Transformer Saturation Compensation for Transformer Differential Relays
Компенсация насыщения трансформаторов тока для дифференциальных реле трансформаторов
2015-03-12
SCID: 54.1/szz5xqt7
Discuss with AI
current-transformer saturation compensationfault and inrush current reconstructionmagnetizing inrush currentsample-by-sample algorithmtransformer differential relays
Figures from the paper
Abstract (AI)
Current-transformer (CT) saturation threatens accurate discrimination between internal fault current and magnetizing inrush current of a transformer and endangers the proper operation of a differential relay. Thus, compensation of CT saturation could substantially improve the performance and security of transformer differential relays. So far, almost all of the technical literature in this field has focused exclusively on fault current compensation. However, this paper proposes an efficient compensation algorithm to reconstruct the fault and inrush currents which are distorted by CT saturation. Some of the attractive features of the proposed method are its accuracy, fast response time, desired sample-by-sample output, no dependency on power system topology, immunity against noise and harmonics, and its simplicity. These features are extracted through the application of numerous test cases reflecting a wide range of variations in fault and inrush currents. The proposed algorithm proves to be fast, accurate, and reliable.
Key Findings
1
Tests across numerous fault and inrush scenarios indicate immunity to noise and harmonics, along with simplicity and reliable operation.
2
The algorithm provides accurate, fast, sample-by-sample outputs without requiring power-system topology information.
3
The paper proposes an efficient algorithm that reconstructs both fault and magnetizing inrush currents distorted by current-transformer saturation.
4
The proposed compensation improves the potential security and discrimination performance of transformer differential relays under CT saturation.
5
Unlike prior work focused primarily on fault currents, the method compensates CT saturation effects in both fault and inrush current conditions.
Research Object
Transformer differential relays with current transformers subject to saturation during internal faults and magnetizing inrush
Research Subject
Accurate, fast, noise- and harmonic-immune reconstruction and compensation of fault and magnetizing inrush currents distorted by current-transformer saturation
Publication Details
Publication Date
2015-03-12
Journal
Publisher
ISSN
Cited by
93
Access Type
Author Information
Download PDF
Subscribe to digest
References available in scid.ai2
Cited by5
Restoration of the current transformer secondary current under core saturation conditions based on ANN2024
Detection of Current Transformer Saturation Based on Machine Learning2024
Prevention of the current transformer saturation by using negative resistance2020
Fast Detection and Compensation of Current Transformer Saturation Using Extended Kalman Filter2019
Framework for current transformer saturation detection and waveform reconstruction2018