Fast compensation of current transformer saturation
Быстрая компенсация насыщения трансформатора тока
2010-10-01
SCID: 54.1/yv5tx8bq
Discuss with AI
current transformer saturationpartial nonlinear regressionreal-time protective relayingsaturation detection and compensationseparable nonlinear least squares
Figures from the paper
Abstract (AI)
This paper presents a novel method for current transformer (CT) saturation detection and compensation. In the method, CT saturation characteristics are represented by a partial nonlinear regression model. The parameters of this model can be estimated rapidly and accurately using both unsaturated and saturated sections of the waveform of a secondary fault current, even in a heavy saturation scenario, where the fault waveform is severely distorted. To reduce the computational load of the estimation, separable nonlinear least squares (SNLLS) method is used to separates the linear and nonlinear parameters of the model, thus reducing the complexity of the estimation. With the fast and accurate parameter estimation, the method can be used for real-time protective relaying. The method has been evaluated on the data obtained from PSCAD/EMTDC simulation. The analysis of the test results shows that the proposed method has superior performance than that offered by conventional compensation algorithms.
Key Findings
1
A novel current-transformer saturation detection and compensation method models CT saturation characteristics using partial nonlinear regression.
2
Fast, accurate estimation enables the method’s application to real-time protective relaying.
3
Model parameters are estimated rapidly and accurately from both unsaturated and saturated portions of secondary fault-current waveforms, including heavily distorted cases.
4
PSCAD/EMTDC simulations show superior performance compared with conventional CT compensation algorithms.
5
Separable nonlinear least squares separates linear and nonlinear parameters, reducing estimation complexity and computational load.
Research Object
current transformer (CT) saturation during secondary fault-current waveforms
Research Subject
fast and accurate detection and compensation of CT saturation for real-time protective relaying
Publication Details
Publication Date
2010-10-01
Journal
Publisher
ISSN
Cited by
21
Access Type
Author Information
Download PDF
Subscribe to digest
References available in scid.ai2
Cited by4
Current-Transformer Saturation Compensation for Transformer Differential Relays2015
Restoration of the current transformer secondary current under core saturation conditions based on ANN2024
Detection of Current Transformer Saturation Based on Machine Learning2024
Current Transformer Saturation Detection Bases On Artificial Neural Networks2023